AAAC6201/ASTM-B399/BS3242/DIN48201/IEC61089

AAAC6201/ASTM-B399/BS3242/DIN48201/IEC61089

分享
  • 产品详情
  • 产品参数

We produce AAAC conductor following the relevant standards strictly, such as ASTM B399, BS3242, DIN48201 Part 6, IEC1089,GB9329 etc.

Also special size is available according to your specification.



U.S.A standard-ASTM B231

Code

Conductor size

Stranding

Section area

Diameter of conductor

Linear mass

Rated strength

D.C. resistance at 20

AWG (MCM)

No./mm

mm2

mm

kg/km

kgf

Ω/km

Akron


7/1.68

15.51

5.04

42.7

502

2.15980


4

7/1.96

21.14

5.89

57.89

685

1.35570

Alton

48.69(4)

7/2.12

24.67

6.35

67.56

799

1.58600


2

7/2.47

33.65

7.42

92.14

1091

0.99870

Ames

77.47(2)

7/2.67

39.26

8.02

107.50

1275

0.85470


1/0

7/3.12

53.49

9.35

146.50

1733

0.62590

Azusa

123.3(1/0)

7/3. 37

62.46

10.11

171.00

2019

0.53650


2/0

7/3.50

67.45

10.52

184.70

2090

0.49740

Anaheim

155.4(2/0)

7/3.78

78.75

11.35

215.16

2447

0.42640


3/0

7/3.93

85.00

11.79

232.70

2641

0.39450

Amherst

195.7 (3/0)

7/4.25

99.20

12.75

271.50

3079

0.33730


4/0

7/4.42

107.20

13.26

293.70

3334

0.31190

Alliance

246.9 (4/0)

7/4.77

125.10

14.30

342.60

3885

0.26780


250.0

19/2.91

126.70

14.58

346.90

3977

0.26510


300.0

19/3.19

152.10

15.89

418.60

4772

0.22060

Butte

312.8

19/3.26

158.50

16.31

434.00

4976

0.21120


350.0

19/3.45

177.30

17.25

485.50

5333

0.18860

Canton

394.5

19/3.66

199.00

18.31

547.40

6016

0.16760



19/3.69

202.70

18.44

555.10

6098

0.16490


450.0

19/3.91

228.00

19.56

624.40

6862

0.14680

Cairo

456.4

19/3.98

235.80

19.89

645.70

7097

0.14310


500.0

19/4.12

253.40

20.60

693.60

7617

0.13220


550.0

37/3.10

278.70

21.67

762.90

8555

0.12000

Darien

559.5

19/4.36

283.50

21.79

776.30

8525

0.11810


660.0

37/3.23

304.00

22.63

832.00

9330

0.11050


650.0

37/3.37

329.40

23.57

909.80

10105

0.10150

Elgin

652.4

19/4.71

330.60

23.55

970.60

9942

0.10120


700.0

37/3.49

354.50

24.46

910.60

10401

0.09464

Flint

740.8

37/3.59

375.40

25.15

1028.00

11013

0.08944


750.0

37/3.62

380.20

25.32

1041.00

11216

0.08796


800.0

37/3.73

405.40

26.14

1109.00

11930

0.08285


900.0

37/3.96

456.30

27.74

1249.00

13460

0.07351

Greeley

927.2

37/4.02

469.80

28.14

1287.00

13868

0.07133


1000.0

37/4.18

506.70

29.24

1388.00

14887

0.06597


1077.4

61/3.38

483.40

30.42

1496.00

15907

0.06120


1165.1

61/3.51

523.70

31.59

1617.00

17233

0.05675


1250.0

61/3.63

633.30

32.67

1733.00

18354

0.05306


1259.6

61/3.65

564.00

32.85

1748.00

18558

0.05248


1348.8

61/3.78

604.20

34.02

1872.00

19884

0.04893


1439.2

61/3.90

644.50

35.10

1997.00

21209

0.04597


1500.0

61/3.98

760.00

35.82

2081.00

22127

0.04414


1750.0

61/4.30

886.70

38.70

2429.00

25798

0.03781




British standard-BS3242

Code

Conductor size

Stranding

Sectional Area

Diameter of Conductor

Linear Density

Rated Strength

D.C. Resistance at 20°C

mm2

No. /mm

mm2

mm

kg/km

kgf

Ω/km

Box

15

7/1.85

18.82

5.55

51

537

1.74950

Acacia

20

7/2.08

23.79

6.24

65

680

1.38400

Almond

25

7/2.34

30.10

7.02

82

861

1.09340

Cedar

30

7/2.54

35.47

7.62

97

1014

0.92810


35

7/2. 77

42.18

8.31

115

1205

0.78040

Fir

40

7/2.95

47.84

8.85

131

1367

0.68800

Hazel

50

7/3.30

59.87

9.90

164

1711

0.54980

Pine

60

7/3.61

71.65

10.83

196

2048

0.45940


70

7/3.91

84.05

11.73

230

2402

0.39170

Willow

75

7/4. 04

89.73

12.12

245

2565

0.36690


80

7/4.19

96.52

12.57

264

2758

0.34410


90

7/4.44

108.00

13.32

298

3112

0.30230

Oak

100

7/4.65

118.90

13.95

325

3398

0.27690


100

19/2.82

118.70

14.10

326

3393

0.27870

Mulberry

125

19/3.18

150. 90

15.90

415

4312

0.21920

Ash

150

19/3.48

180.70

17.40

497

5164

0.18310

Elm

175

19/3.76

211.00

18.80

580

6030

0.15680

Poplar

200

37/2.87

239.40

20.09

659

8841

0.13850


225

37/3.05

270.30

21.35

744

7724

0.12270

Sycamore

250

37/3.22

303.20

22.54

835

8664

0.10930

Upas

300

37/3.53

362.10

24.71

997

10350

0.09156

Walnut

350

37/3.81

421.80

26.67

1162

12053

0.07860

Yew

400

37/4.06

479.00

28.42

1319

13685

0.06921

Totara

425

37/4.14

498.10

28.98

1372

14233

0.06656

Rub us

500

61/3.50

586.90

31.50

1620

16771

0.05662

Araucaria

700

61/4.14

821.10

37.26

2266

23450

0.04047




German  standard-DIN48201 Part 6

Conductor size mm2

Alloy area mm2

Number of wires

Diameter of wire mm

Overall diameter of conductor mm

Linear mass kg/km

Rated tensile strength daN

Maximum resistance D.C. at 20
Ω/km

16

15.89

7

1.70

5.10

43

444

2.0910

25

24.25

7

2.10

6.30

66

677

1.3703

35

34.36

7

2.50

7.50

94

960

0.9669

50

49.48

7

3.00

9.00

135

1382

0.6714

50

48.35

19

1.80

9.00

133

1350

0.6905

70

65.81

19

2.10

10.50

181

1838

0.5073

95

93.27

19

2.50

12.50

256

2605

0.3579

120

116.99

19

2.80

14.00

322

3268

0.2854

150

147.11

37

2.25

15.80

406

4109

0.2274

185

181.62

37

2.50

17.50

500

5073

0.1842

240

242.54

61

2.25

20.30

670

6774

0.1383

300

299.43

61

2.50

22.50

827

8363

0.1120

400

400.14

61

2.89

26.00

1104

11176

0.0838

500

499.63

61

3.23

29.10

1379

13960

0.0671

625

626.2

91

2.96

32.60

1732

17490

0.0540

800

802.09

91

3.35

36.90

2218

22402

0.0418

1000

999.71

91

3.74

41.10

2767

27922

0.0335




International standard –IEC61089 A2

Code

Area

Number of wires

Diameter of wire

Diameter of conductor

Linear mass

Rated strength

D.C.
resistance

mm2

mm

mm

kg/km

kN

Ω/km

16

18.4

7

1.83

5.49

50.4

5.43

1.7896

25

28.8

7

2.29

6.87

78.7

8.49

1.1453

40

46.0

7

2.89

8.67

125.9

13.58

0.7158

63

72.5

7

3.36

10.80

198.3

21.39

0.4545

100

115.0

19

2.78

13.90

316.3

33.95

0.2877

125

144.0

19

3.10

15.50

395.4

42.44

0.2302

160

184.0

19

3.51

17.55

506.1

54.32

0.1798

200

230.0

19

3.93

19.65

632.7

67.91

0.1439

250

288.0

19

4.39

21.95

790.8

84.68

0.1151

315

363.0

37

3.53

24.71

998.9

106.95

0.0916

400

460.0

37

3.98

27.86

1268.4

135.81

0.0721

450

518.0

37

4.22

29.54

1426.9

152.79

0.0641

500

575.0

37

4.45

31.15

1585.5

169. 76

0.0577

560

645.0

61

3.67

33.03

1778.4

190.14

0.0516

630

725.0

61

3.89

35.01

2000.7

213.90

0.0458

710

817.0

61

4.13

37.17

2254.8

241.07

0.0407

800

921.0

61

4.38

39.42

2540.6

271.62

0.0361

900

1036.0

91

3.81

41.91

2861.1

305.58

0.0321

1000

1151.0

91

4.01

44.11

3179.0

339.53

0.0289

1120

1289.0

91

4.25

46.75

3560.5

380.27

0.0258

1250

1439.0

91

4.49

49.39

3973.7

424.41

0.0231



International  standard-IEC61089  A3

Code

Area

Number of wires

Diameter
of wire

Diameter of
conductor

Linear
mass

Rated
strength

D.C.
resistance

mm2

mm

mm

kg/km

kN

Ω/km

16

18.6

7

1.84

5.52

50.8

6.04

1.7896

25

29.0

7

2.30

6.90

79.5

9.44

1.1453

40

46.5

7

2.91

8.73

127.1

15.10

0.7158

63

73.2

7

3.65

10.95

200.2

23.06

0.4545

100

11.0

19

2.79

13.95

319.3

37.76

0.2877

125

145.0

19

3.12

15.60

399.2

47.20

0.2302

160

18.0

19

3.53

17.65

511.0

58.56

0.1798

200

232.0

19

3.95

19.75

638.7

73.20

0.1439

250

290.0

19

4.41

22.05

798.4

91.50

0.1151

315

366.0

37

3.55

24.85

1008.4

115.29

0. 0916

400

465.0

37

4.00

28.00

1280.5

146.40

0.0721

450

523.0

37

4.24

29.68

1440.5

164.70

0.0641

500

581.0

37

4.47

31.29

1600.6

183.00

0.0577

560

651.0

61

3.69

33.21

1795.3

204.95

0.0516

630

732.0

61

3.91

35.19

2019.8

230.58

0.0458

710

825.0

61

4.15

37.35

2276.2

259.86

0.0407

800

930.0

61

4.40

39.60

2564.8

292.80

0.0361

900

1046.0

91

3.83

42.13

2888.3

329.40

0.0321

1000

1162.0

91

4.03

44.33

3209.3

366.00

0.0289

1120

1301.0

91

4.27

46.97

3594.4

409.92

0.0258




China standard –GB9329

Nominal Area

Stranding Number Diameter

Calculated Area

Overall Diameter

D.C.
Resistance

Calculated Breaking Load

Calculated Weight

Continuous Carrying Capacity (A)

mm2

No. mm

mm2

mm

Ω/km

N

kg/km

70

80

90

35

7/2.52

34.91

7.56

0.95165

9.75

95.5




50

7/3.02

50.14

9.06

0.66262

14.00

137.1

159

191

218

70

7/3.57

70.07

10.71

0.47418

19.57

191.6

195

235

369

95

7/4.16

95.14

12.48

0.34921

26.57

260.2

234

285

328

120

19/2.84

120.36

14.20

0.27745

33.62

330.9

270

330

379

150

19/3.17

149.96

15.85

0.22269

41.88

412.2

308

378

436

185

19/3.52

184.90

17.60

0.18061

51.64

508.3

350

431

497

210

19/3.75

209.85

18.75

0.15913

58.61

576.8

377

466

539

240

19/4.01

239.96

20.05

0.13917

67.02

659.6

409

507

587

300

37/3.21

299.43

22.47

0.11181

83.63

825.2

466

581

675

400

37/3.71

399.98

25.97

0.08370

111.71

1102.3

553

695

810

500

37/4.15

500.48

29.05

0.06689

139.78

1379.2

631

798

933

630

61/3.63

631.30

32.67

0.05310

176.32

1742.2

721

919

1078

800

61/4.09

801.43

36.81

0.04183

223.84

2211.7

826

1061

1249

1000

61/4.57

1000.58

41.13

0.03351

279.46

2761.1

933

1209

1429


Part No.
UNAAAC
Type
Bare Overhead
Voltage
MV and HV
Size
10-1500mm2
Conductor
Aluminum 6201
Series
4