309Y/H07V2V2-F/90℃ PVC wire

309Y/H07V2V2-F/90℃ PVC wire

分享
  • 产品详情
  • 产品参数

309-Y / H05V2V2-F

            BS EN 50525-2-11 Flexible Cable


APPLICATION

For internal wiring or supply cords to electrical apparatus,

particularly for use in high temperature zones such as lighting applications. Not suitable for outdoor use.


CONSTRUCTION

Conductor

Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)


Insulation

PVC (Polyvinyl Chloride) Type TI3 according to BS EN 50363

Sheath

PVC (Polyvinyl Chloride) Type TM3 according to BS EN 50363



CABLE STANDARDS

BS EN 50525-2-11 (previously BS 6500, BS 7919 table 41),

BS EN/IEC 60332-1-2



CHARACTERISTICS

Voltage Rating (Uo/U) 300/500V

Temperature Rating

Flexed: 0°C to +90°C

Minimum Bending Radius Fixed: 6 x overall diameter Flexed: 10 x overall diameter


Core Identification

Sheath Colour


DIMENSIONS

UNIQUE PART NO.

NO. OF CORES

NOMINAL CROSS SECTIONAL AREA

NOMINAL THICKNESS OF INSULATION

NOMINAL THICKNESS OF SHEATH

NOMINAL OVERALL DIAMETER

NOMINAL WEIGHT

mm²

mm

mm

mm

kg/km

UN90RVV2X0.75

2

0.75

0.6

0.8

6.3

63

UN90RVV3X0.75

3

0.75

0.6

0.8

6.7

74

UN90RVV3X1

3

1

0.6

0.8

7

86

UN90RVV3X1.5

3

1.5

0.7

0.9

8.1

115

UN90RVV3X2.5

3

2.5

0.8

1

9.7

170

UN90RVV4X0.75

4

0.75

0.6

0.8

7.3

78

UN90RVV4X1

4

1

0.6

0.9

7.9

110

UN90RVV4X1.5

4

1.5

0.7

1

9

140

UN90RVV4X2.5

4

2.5

0.8

1.1

10.8

210

UN90RVV5X0.75

5

0.75

0.6

0.9

8.1

105



CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS
SECTIONAL AREA
mm²

MAXIMUM DIAMETER OF WIRES
IN CONDUCTOR
mm

MAXIMUM RESISTANCE OF CONDUCTOR
AT 20oC

Plain Wires
ohms/km

Metal-Coated Wires
ohms/km

0.75

0.21

26

26.7

1

0.21

19.5

20

1.5

0.26

13.3

13.7

2.5

0.26

7.98

8.21



ELECTRICAL CHARACTERISTICS

Current Carrying Capacity and Mass Supportable

NOMINAL CROSS
SECTIONAL AREA
mm2

CURRENT CARRYING CAPACITY

MAXIMUM MASS SUPPORTABLE BY
TWIN FLEXIBLE CORD

Single-Phase AC
Amps

Three-Phase AC
Amps


0.75

6

6

3

1

10

10

5

1.5

16

16

5

2.5

25

20

5



Voltage Drop

NOMINAL CROSS SECTIONAL AREA
mm2

DC OR SINGLE-PHASE AC
mV/A/m

THREE-PHASE AC
mV/A/m

0.75

62

54

1

46

40

1.5

32

27

2.5

19

16


Part No.
UN90RVV
Type
Residential
Voltage
300/500V   450/750V
Size
0.5-16mm2
Conductor
Class 5 copper
Insulation
90DegreeC PVC
Jacket
90DegreeC PVC
Series
4